Table 1

Calibration methods and the error limits allowed in each method

MetricStandardized byError limitsReferences
RMSEASHRAE Guideline 1410–20%Ali et al. (2021), Al-Shargabi et al. (2022), ASHRAE (2002), Chong et al. (2021), Dahlström et al. (2022), Franceschini and Neves (2022) 
CV(RMSE)ASHRAE Guideline, IPMVP, FEMP15–30% (monthly and hourly results)ASHRAE (2002), IPMVP (2022), Hou et al. (2021), Li et al. (2017) 
MBEASHRAE Guideline, IPMVP, FEMP5–20% (monthly and hourly results)ASHRAE (2002), Franceschini and Neves (2022), Hou et al. (2021) 
NMBEASHRAE Guideline, IPMVP, FEMP5–20% (monthly and hourly results)Ali et al. (2021), ASHRAE (2002), Chong et al. (2021) 
GOFASHRAE Guideline0.5–1%ASHRAE (2002), Chong et al. (2021), Cipriano et al. (2015) 
R2Close to 0.999 (monthly and hourly measurements)ASHRAE (2002), Chong et al. (2021), Singaravel et al. (2018) 

Source(s): Created by the authors, 2023