Table 5

Presumption of uncertain values for input parameters

Uncertain parametersUnitValue rangeCalibrated value
School 1School 2School 1School 2
Boiler efficiency%85–9585–988985
Air infiltrationair changes per hour (ACH)0.1–0.50.1–0.50.20.3
Heating set point°C23–2521–2325Main Building: 22
Atelier Buildings: 23
Natural ventilation1/hWarmer months: 4–8
Colder months: 2–6
LessonBreakLessonBreak
Jan/Feb/Mar/Nov/Dec1–22–42–33–4
Apr/May/Sep/Oct2–44–63–54–6
Jun/Jul/Aug4–66–85–77–8

Source(s): Created by the authors, 2023