Table 1.

Phase 1 daytime acoustic performance (LAeq) by space

BuildingSpaceAverage daytime LeqReference criterion (daytime LAeq)Exceedance (yes/no)Standard deviation of daytime Leq (daily)
Phase 1 buildingLounge GL156 dB(A)45 dB(A) (AS/NZS 2107:2016, lounge/day)Yes3.4–6.1
Corridor GC159 dB(A)45 dB(A) (treat as circulation/communal)Yes3.6–6.9
Bedroom GB352 dB(A)40 dB(A) (ward/bedroom/day)Yes3.5
Activity Rm GA160 dB(A)≤45 dB(A)Yes4.2–7.6
Note(s):

Values report the daytime mean LAeq (07:00–21:59) across the monitoring period, with the standard deviation (daily) calculated from 1-minute LAeq on each monitored day (late Sep–early Oct 2024). Bedroom (GB3) has a relatively stable with lower variability, while communal spaces (lounges, dining rooms and activity rooms) naturally have greater dynamic range and higher variability

Source(s): Authors (2025). Reference criteria are drawn from AS/NZS 2107:2016 for hospital ward bedrooms and communal areas during daytime periods