Table 3.

Total test loads based on PSTR requirements (for a 1.5 m dia. test pile)

Test pile IDTest load criteria #1Test load criteria #2
Max ULS load (MN)2 × ULS load (MN)Max SLS load (MN)3 × SLS load (MN)
142.75* × 0.625***53.42831.65* × 0.625***59.344
2/2 A**43.75* × 0.625***54.68832.40* × 0.625***60.750
342.80* × 0.625***53.50031.54* × 0.625***59.156
Note:

*Loads received from bridge structure engineer for representative 2380 mm dia. production piles as per Table 2; **Latest values received from bridge structure engineer after submission of Issued for Construction design report; ***0.625 is a scaling factor for calculation of test pile load, that is, 0.625 = 1.5/2.4