Table III.

Findings of the surveys

Structure/featureFindings
MicrobesHigh concentrations of different bacteria, fungi and microbes have been detected in several air and material samples
Roof and skylightsWater leakages occurred several times from roof and skylights
Failures in structures due to vandalism
Construction errors
WallsIndication of water damage and microbes in partition walls
External walls not studied on a large scale
Construction errors in external walls
WindowsRecurring water leakages from windows in two classrooms
FloorHigh relative humidity in several areas of the base floor
Unpleasant smell from the base floor
Material emissions from glue on the concrete floor
SewersSmell from sewers
Corrosion in some sewers
Accumulation of debris and dents in rainwater drains
Ventilation and air pressureAir flow in many rooms lower than planned
High negative, 25-30 Pa, air pressure in some rooms compared to outdoors
Blocked ventilating pipes
Indoor environmentCarbon dioxide levels in classrooms were reported to be generally at a normal level
Temperatures in classrooms generally at a normal level
Relative humidity has been occasionally slightly below normal level, relative humidity 20-30%, resulting in a feeling of dry air
YardPooled water close to the building
Plants growing close to the building
Minor slanting of the yard away from the building
No underdrain system
OtherDust, poor standard of cleaning
Cracks in joints of several structures, leaking structures