Table 1.

Condition, requirements and considerations related to the rooms; structures; and systems affecting ventilation strategy

Structure/systemConsiderationRequirements
BasementThe basement is damaged in multiple locations. Excess moisture is measured and microbial smell noted in several placesThe damaged structures of the basement need to be repaired. It must be ensured that the potential impurities, even when the basement is repaired, do not enter the upper floors through shafts. Primarily, facilities for active use should not be located in the basement. Instead, building services equipment or storages may be located there
External envelopeThe external envelope might be microbially damagedDue to potential microbes inside the envelope, negative air pressure in the rooms should be avoided, excluding the rooms with a moisture load. It is not possible to block up all of the air leakages
Two-layered intermediate floorThe intermediate floor contains organic filling, which might have become moistIt must be ensured that if the air pressure changes, the organic filling of the intermediate floors does not spread impurities, harmful for health, into the indoor air
Natural ventilation shaftsVentilation shafts are located next to the doors of classrooms 
Air inletThe size and the number of replacement air valves are deficient 
VentilationThe residential wing has rooms without any ventilation system 
Heating systemThe operation of the heating system is deficient 
Other technical building servicesThe majority of the building service equipment needs to be replaced. It might be possible to preserve heat pipes; radiators; and the exhaust shafts of natural ventilation 
Lift The school needs to be accessible for disabled pupils and thus a lift must be built. However, the lift should not be built into the basement, as the potential impurities from the basement might enter into the upper floors
Attic If air supply units are located in the attic, the incombustible floor needs to be taken down and the roofing deck requires steel holders
Shower rooms Currently, cramped shower rooms are located in the basement. It must be explored whether the shower rooms could be located on the first floor. Thus, a lift will also not be needed in the basement
ClassroomsThe existing classroom division is fairly suitable for new educational requirements 

or Create an Account

Close Modal
Close Modal