Resistance factors recommended for the design of single pile in axial compression for redundant pile groups
| Theoretical analysis | Construction control (field verification)a | Resistance factor (φ)b | ||||||
|---|---|---|---|---|---|---|---|---|
| Driving criteria basis | PDA/Capwap | Retap test 3 d after EOD | Static pile load test | Cohesive | Mixed | Non-cohesive | ||
| Iowa ENR formula | WEAP | |||||||
| Iowa Blue Book | Yes | — | — | — | — | 0·60 | 0·60 | 0·50 |
| — | Yes | — | — | — | 0·65 | 0·65 | 0·55 | |
| Yes | — | — | 0·70 | 0·70 | 0·60 | |||
| Yes | — | 0·80 | 0·70 | 0·60 | ||||
| — | — | Yes | 0·80 | 0·80 | 0·80 | |||
| Theoretical analysis | Construction control (field verification) | Resistance factor ( | ||||||
|---|---|---|---|---|---|---|---|---|
| Driving criteria basis | PDA/Capwap | Retap test 3 d after EOD | Static pile load test | Cohesive | Mixed | Non-cohesive | ||
| Iowa ENR formula | WEAP | |||||||
| Iowa Blue Book | Yes | — | — | — | — | 0·60 | 0·60 | 0·50 |
| — | Yes | — | — | — | 0·65 | 0·65 | 0·55 | |
| Yes | — | — | 0·70 | 0·70 | 0·60 | |||
| Yes | — | 0·80 | 0·70 | 0·60 | ||||
| — | — | Yes | 0·80 | 0·80 | 0·80 | |||
Construction control will be specified on the plans to achieve the target nominal driving resistance
Resistance factors are rounded to the nearest 0·05. Resistance factors should be reduced by 20% for non-redundant pile groups