Table 2.

Possible causes for maintenance issues caused by design defects

System componentDefect SNMaintenance issuePossible causes
Internal environment1Insufficient cooling levelThermostat insensitivity owing to wrong location
Improper selection of cooling coil valves
Sensors are not recalibrated at regular intervals. It may be owing to poor accessibility or poor maintenance practices
2Fungal growth and stains on wallsMoisture entry from the fresh air inlet
Infiltration of external warm air – short circuiting
Moisture carry-over from cooling coil
3Noticeable noise from machines roomsLocation of AHU plant room within occupancy space
Improper selection of the low-static FCU fan type
Poor acoustical insulation of the mechanical room
4Users’ dissatisfaction or discomfortAir from the cooling tower gets sucked by air intakes. It may cause legionella infection
Mold growth in return air plenum
Dumping of cold air or malfunction of VAV terminal/FCU
5Hygiene risk of infections or sick building syndrome (SBS)When air intake sucks air from a cooling tower, legionella infection may be caused
Mold growth in the return air plenum
Cold air dumping at users or malfunction of VAV terminal/FCU
6Foul smellLack or inefficiency of exhaust fans, especially in the toilets and kitchen
7Thermal discomfortTemperature instability resulting from the inadequacy of the HVAC system
8Static electricityInsufficient humidification of outside air coming inside the facility
9Noise or pollution threat from maintenance crews’ movement across corridorsSeveral nonadjacent HVAC technical rooms will result in more trips between them
Location selected for machinery rooms is ill-advised and very close to the patients’ area
Insufficient acoustical insulation for machinery rooms
10Limited HVAC control over some unoccupied spotsSome unoccupied locations have a full operating mode
Air handling unit (AHU) and fan coil unit (FCU)11Fan motor noiseImproper selection of the low-static FCU fan type
Inadequate, fatigued, or rusty vibration isolation
12Corrosion/scaling of cooling coilsSelection of coils and coats, especially in harsh weather locations
A large volume of fresh water is added to refill substantial leaks and the different minerals piles of the coils
The housing is not designed to be adequately sealed, which allows continuous contact with moist air and dampness
13Buildup or dust on coils affecting airflowInsufficient or lack of cleaning because of the poor accessibility for maintenance
Improper filter selection or sizing in the design
14Water leakageCondensate pan material’s poor selection, especially when the material is corrosion-resistant but with low-quality considerations
Fine dust accumulations may block fins
Poor accessibility to clean tubes
15Water retention and buildup on the drain panUndersized drain trap
Drain-off pipe damage because of insufficient pipe fittings design
16Condensation on the exterior of componentsPoor specifications for the casing of the AHU/FCU, which provides insufficient insulation
17Air filter clogging causes air pressure dropsMostly occur when the inlets are located nearby an exhaust outlet or a pollution source such as cooling towers and parking lots
Poor accessibility for maintenance which causes inadequate cleaning for filters or late replacements
When the pressure gauge location is at an inaccessible location or hidden, which inhibits adequate maintenance and calibration
BMS-linked differential pressure (DP) is not added to AHU, which limits real-time monitoring
18Poor maintenance accessibilityCrowded layout of piping and ducting around AHU/FCU
AHU/FCU location at very high levels
Existence of structural obstructions that impede the accessibility
Insufficient or wrong access panels that lead to the above-ceiling AHU/FCU
19Control valves not closing appropriatelyImproper selection of balancing valves of coils
Air distribution and terminal systems20Condensation on air conduits and their componentsInadequate insulation
The diffuser’s location is near an external air infiltration into the facility or near entry areas
Lack of proper recalibration of sensors because of accessibility challenges
21Air leakageFlanged joints are subject to air leakages because of their quality, material selection or sizing
Avoidance of flexible duct connectors
22CorrosionRainwater-related moisture is transported from the fresh air into the ducts
Especially in coastal areas, the wet exhaust inability to drain out the moisture
Especially in coastal areas, AHU-related moisture carry-over into supply air ducts
The lack of a heating coil may increase the chances of corrosion occurrences
23Dirt and stains on ductsInadequate or lack of cleaning of ducts because of poor accessibility for maintenance
24Noisy airflowTurbulence occurrence because of under-sized ducts
Air movement in the ducting system is not balanced
Rapid air movement in the duct system because of insufficient or undersized diffusers
Improper allocation of VAV dampers controls
Unavailability of sound attenuator
25Dumping of cold air or poor air balanceShort-circuiting occurrence causing air to return before it is circulated. This case occurs if a diffuser location is near return air grilles
Blockage of furniture, false ceiling, or equipment for diffusers
Dirt accumulation because of maintenance inaccessibility
Poor selection of diffusers and their layout, which aim cold air directly at users, especially in patient rooms
26Pneumatic controls inefficiencyAir compressor failure, especially the open type
Lack of redundant systems since this system is obsolete and needs frequent maintenance
Chillers27Condenser scalingThe use of the open-loop design of condenser water, mainly in a large application
28Corrosion of inside parts of condenser; face plate and tubesThe tubing material is not resistant to all forms of corrosion
Unaccounted factors of harsh conditions of dust, temperature and humidity
29Refrigerant leakageUnavailability of the refrigerant leakage detection system
30Refrigerant contaminationMoisture occurrence around refrigerant because of leakages of condenser tubes
Air and moisture leak into the chiller, which necessitates purging
Improper selection of refrigerant, which may allow for mixing of metallic moving parts of compressor motor or lubricant
31Leakage from coils (Fins)Fins become blocked with dust which is mainly a location issue
32Surging of the chillerOperating the chiller under its load capacity lower than 25% of its handling capacity. The type of chillers may vary; thus, the effect of this cause varies
Condenser pressure because of corroded tubes that may cause surging
Non-condensable matter increases in the refrigerant, caused by either leakage in the evaporator or periodic purging. This noted for subatmospheric refrigerants
33Noise and noticeable vibrationDamaged or insufficient spring isolators
Poor acoustical insulation around the machine’s locations and mechanical rooms
Compressor aging because of continuous running or repeated start-stop.
34Poor access to maintenanceInsufficient access for system components for maintenance and replacement
Limited space for routine maintenance around machines and parts, especially in mechanical rooms
35Condensation on chilled water pipesInadequate insulation causes the pipes to get cold
36Water is coming out from monitoring devicesRemotely installed, which makes it difficult to fit perfectly due to the accessibility challenge
Cooling tower37BiofoulingOccurs when the cooling tower is not perfectly designed to prevent dirt accumulation and stagnation. This consideration is more critical when treated water is used for cooling
38Corroded body and componentsThe materials of cooling tower components, such as louver and collection basin, are not corrosion resistant
39Condenser water foamingCleaning challenges because of inaccessibility to all parts
40Inadequate heat rejectionObstruction of structures around, above or inside the cooling tower
The cooling tower is located near heat exhausts allowing for short-circuiting
Over supplying or undersupplying of condenser water pump, in which the flow rate is too high to reject heat perfectly
41Poor access to maintenance or replacementImproper consideration for maintenance accessibility in the design
Source: Created by the authors

or Create an Account

Close subscription notice
Close access options