Possible causes for maintenance issues caused by design defects
| System component | Defect SN | Maintenance issue | Possible causes |
|---|---|---|---|
| Internal environment | 1 | Insufficient cooling level | Thermostat insensitivity owing to wrong location |
| Improper selection of cooling coil valves | |||
| Sensors are not recalibrated at regular intervals. It may be owing to poor accessibility or poor maintenance practices | |||
| 2 | Fungal growth and stains on walls | Moisture entry from the fresh air inlet | |
| Infiltration of external warm air – short circuiting | |||
| Moisture carry-over from cooling coil | |||
| 3 | Noticeable noise from machines rooms | Location of AHU plant room within occupancy space | |
| Improper selection of the low-static FCU fan type | |||
| Poor acoustical insulation of the mechanical room | |||
| 4 | Users’ dissatisfaction or discomfort | Air from the cooling tower gets sucked by air intakes. It may cause legionella infection | |
| Mold growth in return air plenum | |||
| Dumping of cold air or malfunction of VAV terminal/FCU | |||
| 5 | Hygiene risk of infections or sick building syndrome (SBS) | When air intake sucks air from a cooling tower, legionella infection may be caused | |
| Mold growth in the return air plenum | |||
| Cold air dumping at users or malfunction of VAV terminal/FCU | |||
| 6 | Foul smell | Lack or inefficiency of exhaust fans, especially in the toilets and kitchen | |
| 7 | Thermal discomfort | Temperature instability resulting from the inadequacy of the HVAC system | |
| 8 | Static electricity | Insufficient humidification of outside air coming inside the facility | |
| 9 | Noise or pollution threat from maintenance crews’ movement across corridors | Several nonadjacent HVAC technical rooms will result in more trips between them | |
| Location selected for machinery rooms is ill-advised and very close to the patients’ area | |||
| Insufficient acoustical insulation for machinery rooms | |||
| 10 | Limited HVAC control over some unoccupied spots | Some unoccupied locations have a full operating mode | |
| Air handling unit (AHU) and fan coil unit (FCU) | 11 | Fan motor noise | Improper selection of the low-static FCU fan type |
| Inadequate, fatigued, or rusty vibration isolation | |||
| 12 | Corrosion/scaling of cooling coils | Selection of coils and coats, especially in harsh weather locations | |
| A large volume of fresh water is added to refill substantial leaks and the different minerals piles of the coils | |||
| The housing is not designed to be adequately sealed, which allows continuous contact with moist air and dampness | |||
| 13 | Buildup or dust on coils affecting airflow | Insufficient or lack of cleaning because of the poor accessibility for maintenance | |
| Improper filter selection or sizing in the design | |||
| 14 | Water leakage | Condensate pan material’s poor selection, especially when the material is corrosion-resistant but with low-quality considerations | |
| Fine dust accumulations may block fins | |||
| Poor accessibility to clean tubes | |||
| 15 | Water retention and buildup on the drain pan | Undersized drain trap | |
| Drain-off pipe damage because of insufficient pipe fittings design | |||
| 16 | Condensation on the exterior of components | Poor specifications for the casing of the AHU/FCU, which provides insufficient insulation | |
| 17 | Air filter clogging causes air pressure drops | Mostly occur when the inlets are located nearby an exhaust outlet or a pollution source such as cooling towers and parking lots | |
| Poor accessibility for maintenance which causes inadequate cleaning for filters or late replacements | |||
| When the pressure gauge location is at an inaccessible location or hidden, which inhibits adequate maintenance and calibration | |||
| BMS-linked differential pressure (DP) is not added to AHU, which limits real-time monitoring | |||
| 18 | Poor maintenance accessibility | Crowded layout of piping and ducting around AHU/FCU | |
| AHU/FCU location at very high levels | |||
| Existence of structural obstructions that impede the accessibility | |||
| Insufficient or wrong access panels that lead to the above-ceiling AHU/FCU | |||
| 19 | Control valves not closing appropriately | Improper selection of balancing valves of coils | |
| Air distribution and terminal systems | 20 | Condensation on air conduits and their components | Inadequate insulation |
| The diffuser’s location is near an external air infiltration into the facility or near entry areas | |||
| Lack of proper recalibration of sensors because of accessibility challenges | |||
| 21 | Air leakage | Flanged joints are subject to air leakages because of their quality, material selection or sizing | |
| Avoidance of flexible duct connectors | |||
| 22 | Corrosion | Rainwater-related moisture is transported from the fresh air into the ducts | |
| Especially in coastal areas, the wet exhaust inability to drain out the moisture | |||
| Especially in coastal areas, AHU-related moisture carry-over into supply air ducts | |||
| The lack of a heating coil may increase the chances of corrosion occurrences | |||
| 23 | Dirt and stains on ducts | Inadequate or lack of cleaning of ducts because of poor accessibility for maintenance | |
| 24 | Noisy airflow | Turbulence occurrence because of under-sized ducts | |
| Air movement in the ducting system is not balanced | |||
| Rapid air movement in the duct system because of insufficient or undersized diffusers | |||
| Improper allocation of VAV dampers controls | |||
| Unavailability of sound attenuator | |||
| 25 | Dumping of cold air or poor air balance | Short-circuiting occurrence causing air to return before it is circulated. This case occurs if a diffuser location is near return air grilles | |
| Blockage of furniture, false ceiling, or equipment for diffusers | |||
| Dirt accumulation because of maintenance inaccessibility | |||
| Poor selection of diffusers and their layout, which aim cold air directly at users, especially in patient rooms | |||
| 26 | Pneumatic controls inefficiency | Air compressor failure, especially the open type | |
| Lack of redundant systems since this system is obsolete and needs frequent maintenance | |||
| Chillers | 27 | Condenser scaling | The use of the open-loop design of condenser water, mainly in a large application |
| 28 | Corrosion of inside parts of condenser; face plate and tubes | The tubing material is not resistant to all forms of corrosion | |
| Unaccounted factors of harsh conditions of dust, temperature and humidity | |||
| 29 | Refrigerant leakage | Unavailability of the refrigerant leakage detection system | |
| 30 | Refrigerant contamination | Moisture occurrence around refrigerant because of leakages of condenser tubes | |
| Air and moisture leak into the chiller, which necessitates purging | |||
| Improper selection of refrigerant, which may allow for mixing of metallic moving parts of compressor motor or lubricant | |||
| 31 | Leakage from coils (Fins) | Fins become blocked with dust which is mainly a location issue | |
| 32 | Surging of the chiller | Operating the chiller under its load capacity lower than 25% of its handling capacity. The type of chillers may vary; thus, the effect of this cause varies | |
| Condenser pressure because of corroded tubes that may cause surging | |||
| Non-condensable matter increases in the refrigerant, caused by either leakage in the evaporator or periodic purging. This noted for subatmospheric refrigerants | |||
| 33 | Noise and noticeable vibration | Damaged or insufficient spring isolators | |
| Poor acoustical insulation around the machine’s locations and mechanical rooms | |||
| Compressor aging because of continuous running or repeated start-stop. | |||
| 34 | Poor access to maintenance | Insufficient access for system components for maintenance and replacement | |
| Limited space for routine maintenance around machines and parts, especially in mechanical rooms | |||
| 35 | Condensation on chilled water pipes | Inadequate insulation causes the pipes to get cold | |
| 36 | Water is coming out from monitoring devices | Remotely installed, which makes it difficult to fit perfectly due to the accessibility challenge | |
| Cooling tower | 37 | Biofouling | Occurs when the cooling tower is not perfectly designed to prevent dirt accumulation and stagnation. This consideration is more critical when treated water is used for cooling |
| 38 | Corroded body and components | The materials of cooling tower components, such as louver and collection basin, are not corrosion resistant | |
| 39 | Condenser water foaming | Cleaning challenges because of inaccessibility to all parts | |
| 40 | Inadequate heat rejection | Obstruction of structures around, above or inside the cooling tower | |
| The cooling tower is located near heat exhausts allowing for short-circuiting | |||
| Over supplying or undersupplying of condenser water pump, in which the flow rate is too high to reject heat perfectly | |||
| 41 | Poor access to maintenance or replacement | Improper consideration for maintenance accessibility in the design |
| System component | Defect SN | Maintenance issue | Possible causes |
|---|---|---|---|
| Internal environment | 1 | Insufficient cooling level | Thermostat insensitivity owing to wrong location |
| Improper selection of cooling coil valves | |||
| Sensors are not recalibrated at regular intervals. It may be owing to poor accessibility or poor maintenance practices | |||
| 2 | Fungal growth and stains on walls | Moisture entry from the fresh air inlet | |
| Infiltration of external warm air – short circuiting | |||
| Moisture carry-over from cooling coil | |||
| 3 | Noticeable noise from machines rooms | Location of AHU plant room within occupancy space | |
| Improper selection of the low-static FCU fan type | |||
| Poor acoustical insulation of the mechanical room | |||
| 4 | Users’ dissatisfaction or discomfort | Air from the cooling tower gets sucked by air intakes. It may cause legionella infection | |
| Mold growth in return air plenum | |||
| Dumping of cold air or malfunction of VAV terminal/FCU | |||
| 5 | Hygiene risk of infections or sick building syndrome (SBS) | When air intake sucks air from a cooling tower, legionella infection may be caused | |
| Mold growth in the return air plenum | |||
| Cold air dumping at users or malfunction of VAV terminal/FCU | |||
| 6 | Foul smell | Lack or inefficiency of exhaust fans, especially in the toilets and kitchen | |
| 7 | Thermal discomfort | Temperature instability resulting from the inadequacy of the HVAC system | |
| 8 | Static electricity | Insufficient humidification of outside air coming inside the facility | |
| 9 | Noise or pollution threat from maintenance crews’ movement across corridors | Several nonadjacent HVAC technical rooms will result in more trips between them | |
| Location selected for machinery rooms is ill-advised and very close to the patients’ area | |||
| Insufficient acoustical insulation for machinery rooms | |||
| 10 | Limited HVAC control over some unoccupied spots | Some unoccupied locations have a full operating mode | |
| Air handling unit (AHU) and fan coil unit (FCU) | 11 | Fan motor noise | Improper selection of the low-static FCU fan type |
| Inadequate, fatigued, or rusty vibration isolation | |||
| 12 | Corrosion/scaling of cooling coils | Selection of coils and coats, especially in harsh weather locations | |
| A large volume of fresh water is added to refill substantial leaks and the different minerals piles of the coils | |||
| The housing is not designed to be adequately sealed, which allows continuous contact with moist air and dampness | |||
| 13 | Buildup or dust on coils affecting airflow | Insufficient or lack of cleaning because of the poor accessibility for maintenance | |
| Improper filter selection or sizing in the design | |||
| 14 | Water leakage | Condensate pan material’s poor selection, especially when the material is corrosion-resistant but with low-quality considerations | |
| Fine dust accumulations may block fins | |||
| Poor accessibility to clean tubes | |||
| 15 | Water retention and buildup on the drain pan | Undersized drain trap | |
| Drain-off pipe damage because of insufficient pipe fittings design | |||
| 16 | Condensation on the exterior of components | Poor specifications for the casing of the AHU/FCU, which provides insufficient insulation | |
| 17 | Air filter clogging causes air pressure drops | Mostly occur when the inlets are located nearby an exhaust outlet or a pollution source such as cooling towers and parking lots | |
| Poor accessibility for maintenance which causes inadequate cleaning for filters or late replacements | |||
| When the pressure gauge location is at an inaccessible location or hidden, which inhibits adequate maintenance and calibration | |||
| BMS-linked differential pressure (DP) is not added to AHU, which limits real-time monitoring | |||
| 18 | Poor maintenance accessibility | Crowded layout of piping and ducting around AHU/FCU | |
| AHU/FCU location at very high levels | |||
| Existence of structural obstructions that impede the accessibility | |||
| Insufficient or wrong access panels that lead to the above-ceiling AHU/FCU | |||
| 19 | Control valves not closing appropriately | Improper selection of balancing valves of coils | |
| Air distribution and terminal systems | 20 | Condensation on air conduits and their components | Inadequate insulation |
| The diffuser’s location is near an external air infiltration into the facility or near entry areas | |||
| Lack of proper recalibration of sensors because of accessibility challenges | |||
| 21 | Air leakage | Flanged joints are subject to air leakages because of their quality, material selection or sizing | |
| Avoidance of flexible duct connectors | |||
| 22 | Corrosion | Rainwater-related moisture is transported from the fresh air into the ducts | |
| Especially in coastal areas, the wet exhaust inability to drain out the moisture | |||
| Especially in coastal areas, AHU-related moisture carry-over into supply air ducts | |||
| The lack of a heating coil may increase the chances of corrosion occurrences | |||
| 23 | Dirt and stains on ducts | Inadequate or lack of cleaning of ducts because of poor accessibility for maintenance | |
| 24 | Noisy airflow | Turbulence occurrence because of under-sized ducts | |
| Air movement in the ducting system is not balanced | |||
| Rapid air movement in the duct system because of insufficient or undersized diffusers | |||
| Improper allocation of VAV dampers controls | |||
| Unavailability of sound attenuator | |||
| 25 | Dumping of cold air or poor air balance | Short-circuiting occurrence causing air to return before it is circulated. This case occurs if a diffuser location is near return air grilles | |
| Blockage of furniture, false ceiling, or equipment for diffusers | |||
| Dirt accumulation because of maintenance inaccessibility | |||
| Poor selection of diffusers and their layout, which aim cold air directly at users, especially in patient rooms | |||
| 26 | Pneumatic controls inefficiency | Air compressor failure, especially the open type | |
| Lack of redundant systems since this system is obsolete and needs frequent maintenance | |||
| Chillers | 27 | Condenser scaling | The use of the open-loop design of condenser water, mainly in a large application |
| 28 | Corrosion of inside parts of condenser; face plate and tubes | The tubing material is not resistant to all forms of corrosion | |
| Unaccounted factors of harsh conditions of dust, temperature and humidity | |||
| 29 | Refrigerant leakage | Unavailability of the refrigerant leakage detection system | |
| 30 | Refrigerant contamination | Moisture occurrence around refrigerant because of leakages of condenser tubes | |
| Air and moisture leak into the chiller, which necessitates purging | |||
| Improper selection of refrigerant, which may allow for mixing of metallic moving parts of compressor motor or lubricant | |||
| 31 | Leakage from coils (Fins) | Fins become blocked with dust which is mainly a location issue | |
| 32 | Surging of the chiller | Operating the chiller under its load capacity lower than 25% of its handling capacity. The type of chillers may vary; thus, the effect of this cause varies | |
| Condenser pressure because of corroded tubes that may cause surging | |||
| Non-condensable matter increases in the refrigerant, caused by either leakage in the evaporator or periodic purging. This noted for subatmospheric refrigerants | |||
| 33 | Noise and noticeable vibration | Damaged or insufficient spring isolators | |
| Poor acoustical insulation around the machine’s locations and mechanical rooms | |||
| Compressor aging because of continuous running or repeated start-stop. | |||
| 34 | Poor access to maintenance | Insufficient access for system components for maintenance and replacement | |
| Limited space for routine maintenance around machines and parts, especially in mechanical rooms | |||
| 35 | Condensation on chilled water pipes | Inadequate insulation causes the pipes to get cold | |
| 36 | Water is coming out from monitoring devices | Remotely installed, which makes it difficult to fit perfectly due to the accessibility challenge | |
| Cooling tower | 37 | Biofouling | Occurs when the cooling tower is not perfectly designed to prevent dirt accumulation and stagnation. This consideration is more critical when treated water is used for cooling |
| 38 | Corroded body and components | The materials of cooling tower components, such as louver and collection basin, are not corrosion resistant | |
| 39 | Condenser water foaming | Cleaning challenges because of inaccessibility to all parts | |
| 40 | Inadequate heat rejection | Obstruction of structures around, above or inside the cooling tower | |
| The cooling tower is located near heat exhausts allowing for short-circuiting | |||
| Over supplying or undersupplying of condenser water pump, in which the flow rate is too high to reject heat perfectly | |||
| 41 | Poor access to maintenance or replacement | Improper consideration for maintenance accessibility in the design |
Sharing content requires targeting cookies to be enabled. Please update your cookie preferences to use this feature.