The purpose of this paper is to study the cause of severe corrosion of the galvanized lightning rods in a 220 kV transformer substation, and to seek the effective corrosion inhibition measures for the hollow lightning rods.
The corrosion morphology and rust component of lightning rod was analyzed, and the corrosion process of lightning rod was researched by means of scanning electron microscopy (SEM), X-ray diffraction (XRD), ion chromatography and electrochemical tests.
The results indicated that the outer surface of hollow lightning rod was corroded slightly; however, its inner surface suffered severe corrosion because of a long time high-humidity environment inside the tube caused by the rainwater permeation. A rust layer consisted of Fe3O4 and a little FeOOH was accumulated on the inner surface of the hollow lightning rod. Moreover, Fe3O4 rust layer worked as a large cathode area which could promote the corrosion of metal substrate further. A self-accelerating corrosion process was formed on the inner surface, making the corrosion failure of lightning rod occurred and aggravated gradually.
The corrosion of inner surface of hollow lightning rod cannot be detected easily. More attention should be paid to the corrosion inhibition of lightning rod. The key of corrosion inhibition for the hollow lightning rod was to avoid the rainwater accumulation inside tube. The research results can provide guidelines on the corrosion inhibition measures selection of lightning rod in transformer substation.