Purpose

This paper aims to present and define a factor to assess the severity supported along transformer windings when the transformer is subjected to a transient voltage waveform due a switching operation of a vacuum circuit breaker (VCB). This factor is identified as time domain severity factor (TDSF).

Design/methodology/approach

Since each of switching waveforms depend on the electrical interaction between transformer and the VCB, it implies that each of those combinations is characterized by a TDSF. To obtain the TDSF implies to manage two different models of the transformer under consideration. Firstly, a terminal model (black box model) of the transformer is built to compute the switching waveform at transformer terminals during VCB operation. Then, a detailed model (white box model) of the transformer is used to compute the internal transient voltage distribution along transformer windings.

Findings

A practical application of a power system consisting of a real transformer connected to a VCB is performed to show the sensibility of the TDSF coefficient.

Originality/value

Previous works found in the literature already consider the evaluation of the overvoltages in transformer associated to switching transient by coefficients, such as the frequency domain severity factor (FDSF). But this factor, as a global coefficient, could not assess the severity along windings to localize dielectrically weak points. Therefore, this paper overcomes this limitation proposing an alternative coefficient identified as time domain severity factor (TDSF).

You do not currently have access to this content.
Don't already have an account? Register

Purchased this content as a guest? Enter your email address to restore access.

Please enter valid email address.
Email address must be 94 characters or fewer.
Pay-Per-View Access
$41.00
Rental

or Create an Account

Close Modal
Close Modal

Gift article access

As a benefit of your subscription, you can share temporary access to restricted articles.

Each link will stop working after 30 days or 10 uses. You may create up to 10 links in a 30 day period.

Please sign in to your personal account to gift article access.

Register

Gift article access

As a benefit of your subscription, you can share temporary access to restricted articles.

Each link will stop working after 30 days or 10 uses. You may create up to 10 links in a 30 day period.

Gift articles remaining: --

Gift article access

Each link will stop working after 30 days or 10 uses. You may create up to 10 links in a 30 day period.

Gift articles remaining: --

Gift article access

As a benefit of your subscription, you can share temporary access to restricted articles.

Each link will stop working after 30 days or 10 uses.

You have reached the limit of 10 links within a 30 day period.