Purpose

The purpose of this paper is to give a comparison between different type of baffles for a better application. Computational analysis of heat transfer and fluid flow through plain, flower and perforated baffles for heat exchanger.

Design/methodology/approach

Numerical simulations for heat exchangers with plain, flower and perforated baffles are carried out with finite volume method. The thermal-hydraulic performance for the three types is presented in the same conditions.

Findings

The perforated baffles generate low shell pressure with high Nusselt number; transverse baffles give the best heat transfer with high pumping power. The overall performance coefficient of these three types of heat exchangers shows that the perforated baffles have a highest and the transverse baffles have the lowest. Analysis of the results show that perforated transverse baffles produce pressure drop lower by 6.68% than transverse baffles and 2.64% lower than flower baffles. The pumping power for perforated transverse baffles lower by 13.3% to the transverse baffles and 4.72% lower than that of flower baffles. The Nusselt number for perforated baffles higher by 4.16% to the flower baffles and 2.77% with transverse baffles. The overall performance factor in the heat exchanger with perforated baffles higher by 5.55% to that with transverse baffles and 3.46% with flower baffles. Recirculation areas are reduced in shell with perforated baffles and velocity distribution becomes more uniform.

Originality/value

Using of perforated baffles in heat exchanger give the best overall performance factor.

Licensed re-use rights only
You do not currently have access to this content.
Don't already have an account? Register

Purchased this content as a guest? Enter your email address to restore access.

Please enter valid email address.
Email address must be 94 characters or fewer.
Pay-Per-View Access
$41.00
Rental

or Create an Account

Close Modal
Close Modal