This paper investigates the failure, bond, strain and stress development of steel bars in a cyclically loaded substandard reinforced concrete beam–column joint. A seismic assessment of 17 existing buildings in a low seismic zone was conducted to study correlations among column size, column depth to bar diameter ratio, bond index and column tributary area. Four half-scale specimens, representing beam–column joints in buildings with various column tributary areas, were tested under quasi-static cyclic loading. The test results reveal brittle joint shear failure in specimens with small and medium column tributary areas and beam flexural failure in specimens with a large column tributary area. By unbonding longitudinal beam bars in the joint, joint shear failure can be prevented. Local pull-out bond and anchorage bond were also studied. All the specimens studied demonstrated the existence of anchorage bond, but local pull-out slip cannot be prevented in all specimens regardless of column depth to bar diameter ratio.
Article navigation
June 2011
Research Article|
June 01 2011
Cyclic stress development in substandard beam–column joint
Panuwat Joyklad, MEng;
Panuwat Joyklad, MEng
Graduate student
School of Civil Engineering and Technology, Sirindhorn International Institute of Technology, Thammasat University, Pathumthani, Thailand
Search for other works by this author on:
Amorn Pimanmas, PhD
Amorn Pimanmas, PhD
Associate Professor
School of Civil Engineering and Technology, Sirindhorn International Institute of Technology, Thammasat University, Pathumthani, Thailand
Search for other works by this author on:
Publisher: Emerald Publishing
Revision Received:
July 01 2009
Accepted:
January 06 2010
Online ISSN: 1751-7702
Print ISSN: 0965-0911
ICE Publishing: All rights reserved
2011
Proceedings of the Institution of Civil Engineers - Structures and Buildings (2011) 164 (3): 211–225.
Article history
Revision Received:
July 01 2009
Accepted:
January 06 2010
Citation
Joyklad P, Pimanmas A (2011), "Cyclic stress development in substandard beam–column joint". Proceedings of the Institution of Civil Engineers - Structures and Buildings, Vol. 164 No. 3 pp. 211–225, doi: https://doi.org/10.1680/stbu.9.00055
Download citation file:
New and popular articles
Suggested Reading
Shear assessment of Della Vittoria stadium, Bari, Italy
Proceedings of the Institution of Civil Engineers - Engineering History and Heritage (February,2010)
Genetic algorithm design of a soil–structure–damper system
Proceedings of the Institution of Civil Engineers - Structures and Buildings (June,2015)
Evaluation of seismic retrofit to existing concrete structures by fluid viscous dampers
Proceedings of the Institution of Civil Engineers - Structures and Buildings (February,2002)
A vector intensity measure to reliably predict maximum drift in low- to mid-rise buildings
Proceedings of the Institution of Civil Engineers - Structures and Buildings (March,2018)
Simplified FE model for RC structures under earthquakes
Proceedings of the Institution of Civil Engineers - Structures and Buildings (April,2006)
Related Chapters
Analysis of progressive failure and cracking in old British dams
Selected papers on geotechnical engineering by P R Vaughan
Tunnelling
The Essence of Geotechnical Engineering: 60 years of Géotechnique
FIELD TRIALS ON COVERCRETE MONITORING SENSORS: A TEMPERATURE CORRECTION PROTOCOL FOR CONDUCTIVITY MEASUREMENTS
Innovations and Developments In Concrete Materials And Construction: Proceedings of the International Conference held at the University of Dundee, Scotland, UK on 9–11 September 2002
Recommended for you
These recommendations are informed by your reading behaviors and indicated interests.